HUD Code by the Numbers: Every Key Figure in One Table

Owners, buyers and installers keep running into the same federal numbers: how wide a door has to be, how far the frame must sit above the ground, how hot the bath water may get. They are all in the HUD Code, but spread across two long federal regulations written for manufacturers, not homeowners.

This page puts the figures people actually ask about in one place. Every number links to the exact section of the regulation it comes from, so you can check it yourself, and to the guide on this site that explains what it means in practice.

Two parts of the federal rules are covered. 24 CFR 3280, the Manufactured Home Construction and Safety Standards, governs how the home is built at the factory. 24 CFR 3285, the Model Manufactured Home Installation Standards, governs how it is set up on site. The construction standard applies to homes built from June 15, 1976 onward. States can add their own rules, especially for installation, and many do.

Doors and exits

RequirementThe number24 CFRGuide
Clear opening, every exterior swinging door28 × 74 in (seals or stops may take up to 1 in)3280.105(b)(2)Exterior doors
Clear opening, at least one egress door (edition in force since Sept. 15, 2025)32 × 74 in, no reduction3280.105(b)(2)Exterior doors
Clear opening, exterior sliding glass door28 × 72 in3280.105(b)(2)—
Number of exterior doorsAt least 2, remote from each other3280.105(a)—
Distance between the two required doors≥ 12 ft (single-wide), ≥ 20 ft (double-wide), center to center3280.105(a)(2)—
Travel from a bedroom door to an exit door≤ 35 ft3280.105(a)(2)(iv)—
Interior privacy locksEmergency release on the outside3280.108(b)Interior doors

Labels and paperwork

RequirementThe number24 CFRGuide
HUD certification label (tag)1 per transportable section, about 2 × 4 in3280.11(a)–(b)HUD tag
Where the label goesTaillight end, about 1 ft up and 1 ft in from the road side3280.11(d)HUD tag
Data plateNear the main electrical panel or another accessible, visible spot3280.5Data plate
What the data plate listsPlant, serial, model, date, label numbers, appliances, roof and wind zones3280.5(a)–(i)Data plate

Fire safety: interior finishes

A flame spread rating measures how fast fire travels across a surface. Lower is safer.

RequirementThe number24 CFRGuide
Walls and partitionsFlame spread ≤ 2003280.203(b)(1)Painting walls
CeilingsFlame spread ≤ 753280.203(b)(2)—
Walls and ceiling around a furnace or water heaterFlame spread ≤ 253280.203(b)(3)Water heaters
Surfaces next to the cooking rangeFlame spread ≤ 50 (backsplashes up to 6 in exempt)3280.203(b)(4)—
Plastic tubs, shower units and doorsFlame spread ≤ 2003280.203(b)(6)Bathtubs

Structure: floors, roofs and framing

RequirementThe number24 CFRGuide
Floor live load40 lb/ft², plus 200 lb on a 1-in disc with ≤ ⅛ in deflection3280.305(g)(1)Soft floors
Floor deflection under design live load≤ span / 2403280.305(d)(1)Tile
Roof and ceiling deflection≤ span / 1803280.305(d)(1)Roof types
Roof design live loadNorth 40 psf · Middle 30 psf · South 20 psf3280.305(c)(3)Roof types
Notch at the end of a joist≤ ¼ of joist depth3280.305Soft floors
Notch in the top or bottom of a joist≤ ⅙ of depth, never in the middle third of the span3280.305Soft floors
Hole bored through a joist≤ ⅓ of depth, ≥ 2 in from top and bottom3280.305Soft floors

Plumbing

RequirementThe number24 CFRGuide
Toilet drain connection≥ 3 in inside diameter, flange fastened to the floor3280.610(d)(1)Toilets
Drain outlet for the whole homeOnly 1, ≥ 3 in inside diameter3280.610(c)Disposals
Clearance around the drain outlet≥ 3 in all round, 18 in unobstructed in front3280.610(c)(2)—
Fixture drain sizes1¼ in (one lavatory) · 1½ in (2–3 fixtures) · 2 in (4+ vented) · 3 in (toilets)3280.610(e)Disposals
Slope of horizontal drain pipe≥ ¼ in per ft (⅛ in with a full-size cleanout)3280.610(h)—
Shower wall height (non-absorbent finish)≥ 6 ft above the bathroom floor3280.607(b)(3)Shower surrounds
Shower receptorSides ≥ 1 in above threshold · depth 2–9 in · floor slope ¼–½ in per ft3280.607(b)(3)Shower surrounds
Hot water to bathtubs≤ 120 °F (ASSE 1070 limiting device)3280.607Bathtubs
Shower and tub-shower valvesPressure-balance or thermostatic (ASSE 1016), stops ≤ 120 °F3280.607Faucets
Plumbing vents through the roof≥ 2 in above the roof, ≥ 3 ft from air intakes3280.611—

Gas, heating and water heaters

RequirementThe number24 CFRGuide
Gas shutoff valve at an applianceWithin 6 ft of a cooking appliance, 3 ft of any other3280.705Furnace not igniting
Fuel-burning appliances (except ranges, ovens, dryers and a few others)Combustion fully separated from the air inside the home3280.709HUD-approved water heaters
Tank water heatersCorrosion-resistant drip pan draining outside or to a drain3280.709(h)Water heaters
Supply air ductsInsulation ≥ R-4 (unless inside R-4 floor or R-6 ceiling insulation)3280.715(a)(6)—
Crossover ducts exposed to outside airInsulation ≥ R-8, vapor retarder ≤ 1 perm3280.715(a)(7)Crossover ducts
Attic or roof cavity ventilation≥ 1/300 of the cavity floor area (≥ 50% high, ≥ 40% low)3280.504(d)(1)—

Installation on site (24 CFR 3285)

RequirementThe number24 CFRGuide
Clearance under the frame≥ 12 in from the lowest main frame member to the grade3285.305Releveling
Shims on a pierIn pairs, driven tight, ≤ 1 in of height3285.304Releveling
Pier lean, top to bottom≤ ½ in (pier under 36 in) · ≤ 1 in (36–67 in) · over 67 in engineer-designed3285.306Releveling
Grade away from the home≥ ½ in per ft for the first 10 ft3285.203(c)Gutters
Ground vapor retarder (skirted homes)6-mil polyethylene over the whole area, 12-in overlaps3285.204Vapor barriers
Crawlspace vents1 ft² per 150 ft² of floor · 1 per 1,500 ft² with a vapor retarder3285.505(a)Vapor barriers
Ground anchor ratingWorking load ≥ 3,150 lb, ultimate ≥ 4,725 lb3285.402Tie-downs

What this page does not cover

State rules. Installation, titling, taxes and park tenancy are largely state law, and several states set stricter installation requirements than 24 CFR 3285. Your state agency is listed in HUD’s directory of state administrative agencies.

Homes built before June 15, 1976. They predate the HUD Code, and none of these numbers is guaranteed to apply.

Your home’s own manual. The installation instructions for your specific home can be stricter than the federal minimum, and where they are, they govern.

Checked against the eCFR edition current through October 20, 2026. Last updated: October 22, 2026. If you find a figure that has changed, tell us and we will correct it.


About the author

I’m Sergio Cobos Juan, and I research and write every guide on Mobile Home Handbook. Each one is built from primary sources — the federal HUD Code (24 CFR 3280 and 3285), state agency documents and manufacturer manuals — and lists them at the end. I’m not a contractor or installer: for gas, electrical, structural or anchoring work, hire a licensed professional.